21.02.045 Fire flow requirements for buildings.
The procedure determining fire flow requirements for buildings or portions of buildings hereafter constructed shall be in accordance with this chapter.
(1) Scope. This section is the procedure for determining fire flow requirements for all buildings or portions of buildings and substantial alterations to all buildings, hereafter constructed. Fire flow requirements are site and building specific. The requirements of this section supersede any conditions, notes, or requirements on any plat that do not meet the requirements of this section.
Nothing in this section shall be deemed to reduce, replace, or waive any water system requirements in the Clallam County Code, including, but not limited to, minimum fire flow and hydrant spacing, nor shall a reduction or exception to fire flow and hydrant spacing requirements reduce or exempt fire flow requirements of this section.
(2) Fire Flow Requirements for Buildings. Prior to the issuance of a building permit for any building, portion of a building, or substantial alteration thereto, fire flow shall be provided in the amount required by this section, including UGA designations.
(a) The fire flow and duration requirements for buildings other than one- and two-family dwellings (R-3) and private garages or agricultural buildings (U) shall not be less than that specified in Table A.
(b) Exception: Buildings for which fire flow is 500 gallons per minute or less, following all applicable modifications, are exempt from fire flow requirements.
(3) Modifications.
(a) Fire Areas. Portions of buildings which are separated into one or more fire areas shall be constructed in accordance with the IBC.
(b) Fire Flow Reduction for Automatic Fire Sprinkler Systems. The fire flow requirement for buildings protected with an automatic fire sprinkler system installed with the water supply provisions specified in NFPA 13 may be reduced up to 75 percent. Fire flow requirements for buildings with a limited supply fire sprinkler system may be reduced 50 percent.
(c) Fire Flow Reduction for Central Station Fire Alarm Systems. The fire flow requirement for buildings protected throughout with an approved automatic fire detection system including approved, UL listed central station monitoring installed in accordance with the provisions of the IFC may be reduced an additional 250 gallons per minute.
Minimum Required Fire Flow and Flow Duration for Nonresidential Buildings |
||||||
---|---|---|---|---|---|---|
FIRE AREA (square feet) x 0.0929 for m2 |
FIRE FLOW (gal./min.)2 |
FLOW DURATION (hours) |
||||
Type I-A, I-B1 |
Type II-A, III-A1 |
Type IV, V-A1 |
Type II-B, III-B1 |
Type V-B1 |
x 3.785 for L/min. |
|
0 – 5,500 |
0 – 3,700 |
0 – 2,600 |
0 – 2,100 |
0 – 1,600 |
500 |
1 |
5,501 – |
3,701 – |
2,601 – |
2,101 – |
1,601 – |
750 |
1 |
7,801 – |
5,001 – |
3,501 – |
2,701 – |
2,001 – |
1,000 |
1 |
11,101 – |
6,801 – |
4,701 – |
3,501 – |
2,401 – |
1,250 |
1 |
15,901 – |
9,301 – |
6,201 – |
4,501 – |
2,901 – |
1,500 |
1 |
22,701 – |
12,701 – |
8,201 – |
5,901 – |
3,601 – |
1,750 |
1 |
30,201 – |
17,001 – |
10,901 – |
7,901 – |
4,801 – |
2,000 |
1 |
38,701 – |
21,801 – |
12,901 – |
9,801 – |
6,201 – |
2,250 |
1 |
48,301 – |
24,201 – |
17,401 – |
12,601 – |
7,701 – |
2,500 |
1 |
59,001 – |
33,201 – |
21,301 – |
15,401 – |
9,401 – |
2,750 |
1 |
70,901 – |
39,701 – |
25,501 – |
18,401 – |
11,301 – |
3,000 |
1 |
83,701 – |
47,101 – |
30,101 – |
21,801 – |
13,401 – |
3,250 |
1 |
97,701 – |
54,901 – |
35,201 – |
25,901 – |
15,601 – |
3,500 |
1 |
112,701 – |
63,401 – |
40,601 – |
29,301 – |
18,001 – |
3,750 |
1 |
128,701 – |
72,401 – |
46,401 – |
33,501 – |
20,601 – |
4,000 |
1 |
145,901 – |
82,101 – |
52,501 – |
37,901 – |
23,301 – |
4,250 |
1 |
164,201 – |
92,401 – |
59,101 – |
42,701 – |
26,301 – |
4,500 |
1 |
183,401 – |
103,101 – |
66,001 – |
47,701 – |
29,301 – |
4,750 |
2 |
203,701 – |
114,601 – |
73,301 – |
53,001 – |
32,601 – |
5,000 |
2 |
225,201 – |
126,701 – |
81,101 – |
58,601 – |
36,001 – |
5,250 |
2 |
247,701 – |
139,401 – |
89,201 – |
65,401 – |
39,601 – |
5,500 |
2 |
271,201 – |
152,601 – |
97,701 – |
70,601 – |
43,401 – |
5,750 |
2 |
295,901 – |
166,501 – |
106,501 – |
77,001 – |
47,401 – |
6,000 |
2 |
" |
" |
115,801 – |
83,701 – |
51,501 – |
6,250 |
2 |
" |
" |
125,501 – |
90,601 – |
55,701 – |
6,500 |
2 |
" |
" |
135,501 – |
97,901 – |
60,201 – |
6,750 |
2 |
" |
" |
145,801 – |
106,801 – |
64,801 – |
7,000 |
2 |
" |
" |
156,701 – |
113,201 – |
69,601 – |
7,250 |
2 |
" |
" |
167,901 – |
121,301 – |
74,601 – |
7,500 |
2 |
" |
" |
179,401 – |
129,601 – |
79,801 – |
7,750 |
2 |
" |
" |
191,401 – |
138,301 – |
85,101 – |
8,000 |
2 |